Fire Pump Motors
Fire Pump motors are for use on fire pumps installed per NFPA-20. All motors meet UL requirements (File # E481231) in open drip proof enclosures designed for relatively clean and dry environments. Foot mounted motors are available from stock in ratings of 10-300 Horsepower and close coupled pump designs are available from stock in rating of 10-100 Horsepower. For custom designs please contact your local Baldor•Reliance sales representative.
Features
• UL File E481231
• 50/60 Hertz
• 200/400V, 230/460V, 460V
• Rolled Steel and Cast Iron Frames
• Exterior Red Paint RAL3002
• Class F Insulation system
• 1.15 Service Factor, 40°C ambient continuous
• Dual voltage motors 20 Hp and larger have 12 leads, suitable for wye-delta or across the line start on either voltage or part winding start on low voltage
• Single voltage motors have 12 leads and are suitable for wye-delta, across the line or part winding start
• Fire Pump motors are not recommended for use with variable frequency drives
Common applications
• UL listed Fire Pump motors installed per NFPA-20
Common industries
• Fire suppression