For oil, petrol and grease separators
Sand - sludge alarm/layer thickness alarm
With EX approval for zone 0
Application
WGA 04 monitors oil, petrol and grease separators for accumulations of sand and sludge and generates an alarm signal when it is time to clean the separator. WGA 05 additionally monitors the thickness of the layer of separated liquid and generates an alarm signal when it is time to drain the separator.
Description
WGA 04 consists of a control unit and an ultrasonic probe (WGA-SN 01). The probe generates an alarm signal when it detects solid matter between the two probe tips. The control unit is equipped with 2 relay outputs, visual and audible alarms as well as Test and Acknowledge buttons. WGA 05 is additionally equipped with a conductivity probe (WGA-SD 03) for monitoring the layer of oil, petrol or grease. The WGA-SD 03 probe is mounted below the constant level of the separator. As soon as the oil, petrol or grease layer reaches the critical level, the device generates an alarm signal. The control unit monitors the probes for short circuits or line interruptions.