Primary Current Injection Tester, It is used in temperature rise or similar load tests of distribution systems such as LV busbar, MV busbar, LV distribution panel, testing of current carrying capacity of switchgear materials, performance tests of industrial electrical devices and many applications that require high current.
Description
The test sample of Primary Current Injection Tester is usually LV Busbar, MV Busbar, LV distribution board, switch, fuse, contactor etc. systems with very low impedance.
In Primary Current Injection Tester, short-time impulse current withstand test, temperature rise test, electrical life test, overload performance test, short-circuit breaking capacity test or similar loading tests, the declared rated current is provided to flow through the test sample and in this way, it tests the test sample. It has the ability to inject current with the same sensitivity to the test sample from the smallest current level to the highest current level.
The maximum capacity of the Primary Current Injection Tester is 10000 A 180 kVA. The maximum current of the product is taken from 4 different outputs and in order to achieve the same level sensitivity at each output, the outputs are designed to be maximum 2500 A. Outputs of Primary Current Injection Tester can be configured according to desired current and voltage values by connecting serial and/or parallel. It can be designed together with the power supply when it is requested not to be affected by the fluctuations in the mains voltage or to perform experiments at different frequencies.