Description
The volume booster with transmission ratio amplifies the outlet pressure at a 1:1 up to 1:6 ratio by a pneumatic pilot pressure, which has no constant bleed. That signal pressure has the same function as a spring in a common regulator: generating counter pressure on the diaphragm. This force is compensated by the outlet pressure on the diaphragm's bottom side. The ratio of pilot pressure to outlet pressure dépends on the size of the operating diaphragms.
Media
compressed air or non-corrosive gases
Supply pressure max. 17 bar
Pilot pressure
max. 10 bar at 1:1 ratio, 5 bar at 1:2, - 3.3 bar at 1:3, - 1.7 bar at 1:6, pilot port G1/4
Accuracy
at supply variation of 3.5 bar: < 7mbar1:1,< 10 mbar at 1:2, < 21 mbar at 1:3, < 41mbar at1:6
response sensitivity: - < 2 mbar 1:1, < - 3 mbar at 1:2, < 17 mbar at 1:3, < 23 mbar at 1:6
Air consumption
max. 3 l/min. subject to outlet pressure
Relieving function
relieving
Relief capacity
170 l/min at 1.5 bar outlet and 0.7 bar overpressure above setpoint
Gauge port
on both sides of the body. thread equal to regulator thread - Mounting position any
Température range
0 °C to 70 °C / 32 °F to 158 °F, for appropriately conditioned compressed air down to -40 °C / -40 °F
Material
Body: zinc die-cast Elastomer: NBR/Buna-N Inner valve: brass and stainless Steel