The pressure transmitter is mainly applied to measure pressure, negative pressure, absolute pressure and other parameters of gas, liquid or vapor, then to convert these parameters into 4~20mA DC. It can connect with HART manipulator to make self-diagnosis, reset measuring range and set zero automatically. The pressure transmitter δ cell receives measured pressure from one side, meanwhile, connects with the air to detect pressure or negative pressure.
Zero migration volume
Maximum zero positive migration volume:difference between migration volume upper range and measuring range
No negative migration volume
Measuring range
Lower range limit:-100%URL (≥-0.1MPa)~+100%URL-Span
Upper range limit:-100%URL+Span (≥-0.1MPa+Span)~+100%URL
Measuring range and zero adjustment
HART manipulator, local button, HART protocol supported by communication software.
Response time
When the electrical damping of the transmitter is turned off, the response time of the step input applied to the transmitter from 10% to 90% of the output range is less than or equal to 0.4s.
Measuring object: liquid, vapor and gas
Accuracy: 0.1% F.S
Range ratio: 100:1
Insulation resistance: >100MΩ (100VDC)
Damping value: 0.1~16s (Optional)
Temperature affecting value: 0.1%F.S/10℃
Output signal: 4~20mA(Max 22mA,Min 3.8mA)
Communication interface: HART
Intrinsic safety: EX ia IIC T6