• linear processing of the measured temperature or other measure into a current and voltage signal
• input (programmable):
• resistance: 0÷2500 Ω
• two independent configurable outputs:
• current 0/4÷20mA (active output, cannot be supplied in two-wire current loop)
• voltage 0/2÷10V
• programmable alarms for exceeded setpoints with hysteresis
• input type, processing range and other processing parameters configured with AR950, AR956 programmer or AR956 programming set or by the manufacturer according to customer specifications
• processing ranges: any in the input measuring range
• signalling the exceeded processing range, sensor error or alarm output status (on-off type):
• optical: red LED
• output signal
• triple galvanic separation(input / output / power): 1.5 kV, 50 Hz, 1 min
• housing for mounting on 35 mm DIN rail
• high accuracy and immunity to interference
• outputs (programmable):
• current: 0/4÷20 mA, 20÷0/4 mA, Ro ≤ 500 Ω
• voltage: 0/2÷10 V, 10÷0/2 V, Rw > 2.5 kΩ
• power supply: 24Vac/dc (18÷50 Vdc, 13÷35 Vac),
• response time (10÷90%): 360ms, programmable in the range of 240÷1600ms
• operating temperature range: 0 ÷ 65 °C
• relative humidity range: 0 ÷ 90 % (no condensation)
• ingress protection rating: IP20