The TPIv-SI series has intrinsically safe inputs: they are associated equipment to be placed in a safe area or ATEX/IECEx area 2.
Easy programmable on the front face with the LCD touchscreen micro-console or via SlimSet PC software.
TECHNICAL SPECIFICATIONS
PROGRAMMABLE SIGNAL CONDITIONER ATEX INTRINSIC SAFETY
Marking: II 3 (1) G Ex ec nC [ia Ga] IIC T4 Gc
Universal bidirectional IS input: mA,mV,V,TC,PT100,potentiometer resistance
1 analog output: voltage or current (active/passive)
Accuracy: 0.1%
Scale factor programmable
Supply for 2-wire sensor
For DIN rail mounting
Programmable by software or tactile µconsole (optional)
Universal power supply: 20 to 250 vac and 20 to 250 vdc