Differential pressure / flow controller MODBUS - DPC200-MOD
Electromechanical diaphragm measuring systemConfiguration via Modbus communication
Selectable measurements (differential pressure or volume flow)
Selectable units (Pa / InH20 or m3/h or cfm)
Selectable control mode or measuring mode
Control mode with adjustable: setpoint, maximum output voltage, P and I parameterd for PI-algorithm, direct or inverse sense
Adjustable k-factor for volume flow calculation
Analog output 0...10 V
The DPC200-MOD has been developed to bundle functions needed in the HVAC industry into one device. As a precise differential pressure sensor it can transmit measurements for both pressure and air flow. The integrated PI control logic is an important component in decentralized closed loop control systems, where pressure and air flow have to be constantly controlled.
The additional Modbus RTU interface is intended for the digitalisation of industrial processes. All device parameters can be read and written with the Modbus RTU interface.
For direct analog processing, a 0 ... 10 V signal output is available. This signal can be configured as a linear / square root measuring signal, or as a manipulated variable of the closed loop controller.
It can be used, for example, in air-conditioning technology for controlling fans, monitoring room pressure or controlling filters.
TECHNICAL SPECIFICATIONS:
Operating mode:
Measuring mode or control mode
Measuring medium:
Air or non-aggressive gases
Measuring principle:
Electromechanical diaphragm measuring system
Measuring unit:
Pa / inH2O or m3/h or cfm