The Rosemount 975UR UV/IR flame detector senses radiant energy in the short wave section of both the ultraviolet and infrared portions of the electromagnetic spectrum and can detect hydrocarbon-based fuel and gas fires. The signals from both sensors are analyzed for frequency, intensity and duration. Simultaneous detection of radiant energy in both the UV and IR sensors triggers an alarm signal. The UV sensor incorporates a special logic circuit that helps prevent false alarms caused by solar radiation.
Specifications
Communication ProtocolOptional HART™ communications on the 0-20 mA analog current (FSK) - used for maintenance, configuration changes and asset management, available in mA source output wiring options. RS-485 Modbus compatible communication link that can be used in computer controlled installations
Ambient TemperatureOperating: -76 °F to +185 °F (-60 °C to +85 °C)
Storage: -76 °F to +185 °F (-60 °C to +85 °C)
Enclosure RatingStainless Steel 316L with electro polish finish
Heavy duty copper free aluminum (less than 1%), polyurethane painted
MountingStainless Steel 316L with electro polish finish
DimensionsDetector 4"x 4.6"x 6.18"(101.6 x 117 x 157 mm)
WeightDetector (stainless steel 316L) 6.3 lb (2.9 kg)
Detector (aluminum) 2.8 lb (1.3 kg)
Tilt mount 2.5 lb (1.1 kg)
Certifications/Approvals
ATEX and IECEx:
Ex II 2 G D
Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T110 °C Db
(Ta -50°C to +85°C) IP66/68