Electro-pneumatic converter for field mounting
-Input 0… 20mA/4… 20mA
-Input resistance: 200 Ω
-Output: 0.2… 1 bar, 3… 15 psi
-Air flow: 2.5 m3/h
-Feature: linear, direct or inverse
-Accuracy: better than 0.5%
-Hysteresis: less than 0.3%
-Influence of the supply air pressure: less than 0.3%/0.1 bar
-Influence of temperature: on zero 0.5% /10°C; on full scale 0.5% /10°C
-Zero calibration: 3 psi ± 3%
-Span Calibration: 15 psi ± 2%
-Power supply: 20 ± 1.5 psi
-Air consumption: 0.08 m3/h