• NAMUR SERIES - diameters 14 - 16 - 18 mm
• Non amplified in d.c. 2 wires
• Cable output
Technical data:
• Working voltage: 5 ÷ 30 Vdc
• Supply voltage according to NAMUR: 7,7 ÷ 9 Vdc
• Max ripple: 10%
• Consumption at 8,2 V with Rx = 1000 Ω
with metal: ≤ 1 mA
without metal: ≥ 3 mA
• Temperature range: - 25° ÷ + 70°C
• Max thermal drift of sensing distance Sr
: ± 10%
• Repeat accuracy (R): 2%
• Cable conductor cross section: 0,35 mm2 on 14 ÷ 16 mm
0,50 mm2 on 18 mm
• According to EN60947-5-6
• Electromagnetic compatibility (EMC) according to EN60947-5-2
• Shock and vibration resistance according to EN60068-2-27 EN60068-2-6
• For certified ATEX version see ATEX Catalogue
Materials:
• Cable: 2 m PVC CEI 20 - 22 II; 90°C; 300 V; O.R.
• Housing: nickel plated brass
• Sensing face: plastic