These sensors are able to detect the presence of a metal blade into the slot. The switching point of the output happens when about the 70% of internal faces is covered by the blade. The special material of the housing allows the use without additional protections against electrostatic charges. Technical data:
•Max ripple: 10%
• Consumption at 8,2 V with Rx = 1000 Ω with metal: ≤ 1 mA without metal: ≥ 3 mA
•Max thermal drift of sensing distance Sr : ± 10%
• Repeat accuracy (R): 2%
• Cable conductor cross section: 0,75 mm2
•Marking: II 1D Ex iaD 20 T80° C II 1G Ex ia IIC T6
• Certified IMQ 08 ATEX 010
• Electromagnetic compatibility (EMC) according to EN60947-5-2
• According to: EN60947-5-6/EN60079-0/EN60079-11/EN60079-26
• Shock and vibration resistance according to EN60068-2-27/EN60068-2-6 Safety parameters:
• Vi max 13,5 V
• Ii max: 60 mA
• Ci max: 100 nF
• Li max: 100 μH
• Pi max: 200 mW These sensors must be used in conjunction with associated apparatus (See Sect. E) Use in hazardous area according to instruction manuals
Materials:
• Cable: 2 m PVC CEI 20 - 22 II; 90°C; 300 V; O.R.
• Housing: plastic