RELAY OUTPUT •
1 or 2 channels •
General Features:
These units allow to amplifiy signals from NAMUR sensors or contacts. The relay outputs have changeover N.O. + N.C. contacts electrically insulated from each other,
from power supply and from all the inputs. When used for NAMUR sensors, the indication of failures is visible with a red LED on the front panel for interruptions or short
circuits on the input lines. The configuration dip-switches are easily accessible removing the front panel. Suitable for DIN rail mounting.
Technical data:
• Supply voltage: see ordering references
• Frequency of power supply: DC or 50 - 60 Hz
• Power consumption max: see ordering references
• According to EN60947-5-6
• Electromagnetic compatibility (EMC) according to EN61000-6-2/-4
INPUT PARAMETERS
• Switching point to ON: ≥ 1,75 mA
• Switching point hysteresis: 0,2 mA
• Failure detection thresholds: open circuit detection when I 7,45 mA (Ri < 100 ohm)
OUTPUTS
• Output function: NO + NC (SPDT)
• Maximum contact voltage: 250 V
• Rated current: 5 A
• Activation/release typical time: 5/2 msec
• Bouncing on N.O./N.C. contacts typical: 1/5 msec