• Portable Insulation Fault Case
• Application main and control circuits
• Current probes Ø 20/52/115 mm
• Residual current measurement in TN/TT systems
• Universal system concept
• Mobile insulation fault location systems for IT systems AC 42…460 Hz 0…790 V/DC 0…960 V or deenergised systems
• Residual current measurement in TN/TT systems
• Use in main and control circuits
• Measuring clamps 20/52 mm (115 mm optional)
• Robust aluminium case, convenient to carry
• Test devices PGH18… with variable test current 1…25 mA
• Integrated test voltage for deenergised systems (PGH186)
•
• Insulation fault evaluator EDS195PM
• Backlit LC display, 3 x 16 characters
• Measuring clamps 20/52 mm included in the scope of delivery
• Supplied by an accumulator (delivered with a power supply unit)
• Response value insulation fault location 2…10 mA for main circuits
• Response value insulation fault location 0.2…1 mA for control circuits
• Response value residual current measurement 10 mA…10 A
• Selectable operating mode insulation fault location/residual current measurement
IT systems without installed insulation fault location system (EDS)
• EDS3090PG
• for main circuits up to AC 20…575 V 42…460 Hz, DC 20…504 V with AGE185 up to AC 500…790 V 42…460 Hz, DC 400…960 V
• EDS3091PG
• for control circuits up to AC 20…265 V 42…460 Hz, DC 20…308 V
• EDS3096PG
• for main circuits in IT systems up to AC 0…575 V 42…460 Hz, DC 20…504 V, with all poles disconnected
• EDS3096PV
• for photovoltaic systems with PGH186 up to 20…575 V 42…460 Hz, DC 20…504 V with AGE185 up to AC 500…790 V 42…460 Hz, DC 400…960 V