Three-phase protection relay LXPRC/S/F
over-voltageunder-voltagephase sequence

Three-phase protection relay - LXPRC/S/F - Broyce Control - over-voltage / under-voltage / phase sequence
Three-phase protection relay - LXPRC/S/F - Broyce Control - over-voltage / under-voltage / phase sequence
Add to favorites
Compare this product
 

Characteristics

Measured/monitored value
over-voltage, under-voltage, phase sequence, phase loss
Network
three-phase
Mounting
DIN rail
Other characteristics
time delay
Trigger voltage

415 V

Description

LXPRC/S/F - Under and Over voltage monitoring (Window) - Monitors own three phase, 3-wire supply - Detects incorrect phase sequence and phase loss - Fixed Trip levels/adj. Time delay - SPDT Relay output - 17.5mm wide, DIN Rail mount - UL Listed The product monitors it’s own three-phase supply and for the output relay to energise, all phases must be present, the phase sequence correct and the phase to phase voltages within the fixed Under/Over trip levels. If any of these conditions are not met, the relay will de-energise. Specification - Monitoring function: Under/Over voltage - Monitored supply voltage: 415VAC - Trip level (fixed): Under: 360V/Over: 457V - Hysteresis: ≈2% - Time delay: 0.2 – 10s - Output: SPDT 8A @ 250V (AC1) - Dimensions(mm): W:17.5 x H:89 x D:66.5