Overall screened, unarmoured, fire resistant instrumentation cable
Safety extra-low voltage cables used in petroleum and petrochemical units, particularly for the transmission of AC or DC analogue signals. Unarmoured cables are used when there is no risk of mechanical damage (control room for example) Fire Resistance according to IEC 60331. Sheaths are resistant to aliphatic hydrocarbons
Flame Retardant
Fire Retardant
EM Interferences Resistant
UV Resistant
ROHS Compliant
STANDARDS
NF M87-202 UTE C 32-014 NF C 32-020
IEC 60332-1 IEC 60332-3-24 IEC 60331
CONSTRUCTION
Conductors: Solid (Class1) / stranded (Class2) annealed Copper, acc. to IEC
60228.
o Model 05: 1 x 0,80 mm. – Section = 0,50 mm2
o Model 09: 7 x 0,40 mm. – Section = 0,88 mm2
o Model 15: 7 x 0,52 mm. – Section = 1,50 mm2
o Model 25: 7 x 0,67 mm. – Section = 2,50 mm2
Insulation: Mica tape + XLPE
Cabling elements: Pairs or Triads (Quad configuration for 2-pair cable).
Core Identification: Natural / Red / Blue / Yellow. Numbered on Natural
conductor.
Core. Units are assembled together spirally in concentric layers.
Core wrapping. PETP tape. Minimum 30% overlap.
Collective screen. Tinned cooper drain wire under and in contact with
aluminium/PETP 12/23 laminated tape applied metallic side down.
Outer Sheath: LSZH compound, acc. to EN 50290-2-29. Hydrocarbon Resistant
Sheath marking : The outer sheath shall be marked in white or black ink, at regular intervals, with the following information:
o Name of manufacturer/ Year/ Length marks
o Other type of marks according to the costumer