Dry type frequency injection transformer installed in the HVB/HVA source stations in the building, enabling the injection of remote control signals.
An injection unit comprises 3 transformers, positioned side-by-side, inside, in a well ventilated room (ambient temperature between - 5°C et + 40°C), free of dust and condensation.
• Transformers for interior installation.
• Crystal-oriented iron-silicon sheet magnetic circuit
• Coils with copper or aluminium conductor strips.
• Insulation made of class H metal aramid fibres.
• AN cooling mode.
• Lifting by the 2 rings located on the top of the device.
• Power throughput 40 MVA: MV network voltage of 15 or 20 kV Three-phase short-circuit current at 50 Hz of 12.5 kA
• Power throughput 70 MVA: MV network voltage of 15 or 20 kV Three-phase short-circuit current at 50 Hz of 22 kA
• Injection frequency 175/188Hz
• The size and the design of the connection ranges of these devices permits interchangeability with injection transformers belonging to the previous technical levels without needing to modify the existing installation.