Neutral point coils (zig-zag coupling) are used to earth a neutral via high impedance..
The neutral point three-phase coils are located in the HVB/HVA source stations and connected to the MV network. Neutral point three-phase coils allow:
• The creation of an artificial neutral point
• The introduction of a defined impedance between this neutral point and the earth, in order to limit the current during phase-earth faults on the network.
• Hermetic structure, in a mineral oil bath, for an exterior installation.
• Frame supporting a crystal-oriented iron-silicon sheet single-phase magnetic circuit.
• Copper coils.
• Insulation made of class H metal aramid fibres.
• ONAN cooling mode.
• Lifting by the 2 rings located on the cover.
• Operating reliability: Exceptional mechanical resistance in terms of electro-dynamic force due to coils bonded with epoxide resin*.
• (*Qualification tests defined by the EDF HM-24/94/021 B specification dated 17/07/95, conducted in the Renardières Electrical Engineering Laboratory).
• Endurance of inductances against thermal shocks caused by repeated neutral currents during operation (solid insulation with a thermal index > 180°)