The analog switching relay works in accordance with the phase angle control principle, i.e., the output switching point in the AC sine wave depends on the control input which can be either 4-20mA, 0-10VDC or 0-5VDC. 4mA or 0VDC correspond to zero output power whilst 20mA, 10VDC, 5VDC correspond to full output power ( near linear power response ). The relay switches off every time the output current crosses zero, and switches ON in accordance with the applied control input.
Switching voltage: 180-530Vac -
Input: 4-20mA/0-10V/0-5Vdc
Ie: 50A, 50A, 75A -
Supply power: 10-32Vdc
Peak voltage: 1200V -
Protec: RC and VDR
Indicator: Green LED -
Leakage current: 5mA
Protection level: IP20
Outputrange: 0-99%
Conformity: IEC/ EN60947-4-3