Electronic relay for protection and continuous voltage monitoring.
Protection against voltage surges, triggers at voltages higher than 265 V. Trigger time according to the voltage value less than or equal to:
300 V triggers after 3 s
350 V triggers after 800 ms
400 V triggers after 200 ms
Protection against voltage drop, triggers at voltages less than 160 V. Fixed trigger time of 300 ms.
Error in phase sequence (incorrect phase connection order for RV-T. Fixed trigger time 1 s.
The RV-TS type does not include phase sequence monitoring.
Activation by external input (TRIGGER). Trigger time less than or equal to 10 ms.
Indication LEDs for power supply and voltage error.