DM2 is the range of combined devices for discharging induced transient overvoltages (Type 2 / Class II), and also provides fine protection for sensitive equipment (Type 3 / Class III). Complete with a built-in EMI filter. DIN rail monobloc format.
Features
• Suitable as the final stage of protection in installations with electromagnetic disturbances which might interrupt, degrade of limit system performance.
• Series connection for applications up to 20 A rated current.
• With electromagnetic interference (EMI) filter. Common mode attenuation of the filter is up to 82 dB.
• Maximum discharge current with an 8/20 μs waveform. Imax: 20 kA.
• Combined voltage pulse with 1.2/50 μs waveform. Uoc: 6 kV.
• Single-phase 120 V and 230 V networks.
• Remote and visual indication of life status of the protection device.
Standards and certifications
• IEC 61643-11
• EN 61643-11
Applications
• Building
• E-Mobility - EV charging
• Industry
• Telecom
• Water treatment