Pump control system
Individual pump control up to four pumps
Electronic control
Lead/lag sequencing
On/off or variable speed drive pump control
The PCS is a simple pump control system with lead/lag sequencing on a timed rotation, "first on first off" basis, or manual rotation (user-selectable).
Pump lead/lag on timed rotation
On/off or variable speed pump control of up to 4 pumps
PLC controlled
Modbus RTU communications
Data logging to optional Micro SD card
User-selectable set points
Pumps are turned on or off as required to maintain a pressure set point within a user-configurable deadband. The PCS can control from 2 to 4 pumps for either on-off or VSD control. Data is available via Modbus RTU communications or logged to an optional Micro SD card.