Controls the position of hazardous machine doors/cases with integrated self-checking
Contactless coded sensor with electronic technology and relays
IP68 PA6 / IP69K INOX316L
Performance level and category without external controller: Cat 3 PL=d according to ISO 13849-1
Performance level and category with AWAX controller: Cat 4 up to PL=e
Integrated safety level: SIL 2 according to IEC 61508
• Level of performance without an external controller: PL = d
• Level of performance with AWAX controller: up to PL = e
• Safety category without an external controller: 3
• Safety Integrity Level: SIL 2
• Cycle after dangerous failure: B10d = 2,000,000 at 2A
• Max. activation distance: 10 mm, 2 mm hysteresis
• Security contacts / diagnostics AMX5 / AMX5CM12 : 2 x NO 2A / 48V redundant / 1 x PNP 250mA auxiliary
• Security contacts AMX4: 2 x NO 2A/48V redundant
• Security contacts / diagnostics AMX3 : 1xNO 2A / 48V redundant (2 series contacts) / 1xNF 250mA auxiliary
• Detection encoding: mono-code inviolable
• Indicator: LED indicates code recognition
• Reset: automatic
• Attachment: 4 tamper-proof M4 screws (optional ref: BH4)
• Mounting position: 2 (double wall brackets)
• Material: PA6 or INOX 316L mirror polished (AMX3-OX/AMX5-OX ?or PC (AMX5CM12)
• Electrical Connection: 3, 6, 12m (UL2464 PVC) or 50cm cable with M12 connector (UL20549 PUR) (ref + MKT) or M12 metal base (AMX5CM12)
• Water resistance: IP 68 (PA6) or IP 69K with stainless steel - new generation
• Temperature: -25°C to +60°C