ELR-2 External CT. 2 operation thresholds. Flag indicator (TRIP). Fail safe.
Earth leakage relay with 2 operation thresholds, flush mount. External CT. Fail safe.
Introduction
Range ELR
Product name ELR-2
Product type Residual current protection relay
Current sensors compatibility CT-1 earth leakage current sensor
Technical characteristics
Application Residual current protection relay
Supply voltage 240/415 VAC 50/60Hz
110 VAC/DC
24/48 VAC/DC (optional)
12 VAC/DC (optional)
Power consumption 5,5 VA
Type of measurement Earth fault current internal measurement
Residual earth-leakage adjustment type 0,025...25 A
Residual earth-leakage time delay adjustment type 0,02...5 s
Earth-leakage protection class Type A
Test function Local
Remote test
Output relays 2 changeovers (both TRIP)
5 A (240 VAC)
Configurable normally de-energised or energised
Display indications Green LED (power ON)
Red LED (TRIP
Red LED (ALARM)
Mechanical trip memory (version ELR-2M)
Mounting mode Flush mount 96x96 mm
Standards IEC/EN 61010
IEC/EN 61000-6-2EN
IEC/EN 61000-6-3
IEC/TR 60755
CEI EN 60947-2 Annex M
Weight 280g
Environment
IP degree of protection IP40 front
IP20 terminals
Relative humidity 5...90%
Operating temperature -10...+60 °C
Storage temperature -20...+80 °C
Options
Tropicalization
3rd harmonic filter
Transparent cover IP65