ELR-51AS Residual-current protection relay. Latch relays. Events log. RS485 Modbus. TRIP memory feature.
Earth differential relay with associated toroidal sensor input, measures the leakage current in an electrical installation to detect levels that could be harmful. Ideal for protection or alarm, the product offers multiple settings. 2 relay outputs (bistable) each with 1 changeover contact. RS485 & egrave; available. The non-volatile memory maintains the trip status of the relay.
Introduction
Range ELR
Product name ELR-51AS
Product type Residual current protection relay
Current sensors compatibility CT-1 earth leakage current sensor
Technical characteristics
Application Residual current protection relay
Supply voltage 110-230 VAC 50/60Hz
24/48 VAC/DC (optional)
Power consumption 6 VA
Display type Backlight LCD (red TRIP)
Backlight LCD (yellow ALARM)
Type of measurement True RMS
Earth fault current internal measurement
Residual earth-leakage adjustment 0,030...5 A
Residual earth-leakage time delay adjustment 20...500 ms
Alarm threshold setting 50...90%
Earth-leakage protection class Typo A super immunized
Filter 3rd harmonic filter selectable
Test function Local
Remote test
Output relays 2 independent (latch relay)
5 A (240 VAC)
Configurable normally de-energised or energised
MEMORY function Non-volatile memory retains the trip status of the relay. If tripped, and the supply voltage disappeared, the ELR-51AS will remain tripped at power on, with the trip relay energized and the TRIP LED on, until reset.
Display indications Green LED (power ON)
Red LED (TRIP)
LED OK (System healthy)
Communication port RS485 (optional)
Communication protocol Modbus a 4,8...