RI-R60 Insulation monitoring device up to 760 VAC. Trip and alarm threshold.
Insulation monitoring devices for fault detection network up to 760 VAC
Introduction
Range RI
Product name RI-R60
Product type Insulation monitoring device
Application Production plant protection
Motor protection
Transformation lines protection
Earthing system IT
Technical characteristics
Network voltage 500...760 VAC at 50...60 Hz
Auxiliary supply 110...230 VAC 50/60Hz
Power consumption 5 VA
Type of measurement Network insulation resistance
Intervention threshold Alarm: 30...300 kOhm
Trip: 10...100 kOhm
Response time < 5 s
Measurement current 0,240 mA (max)
Measurement voltage 48 VDC
Internal impedance 200 kOhm
Test function Local
Remote test
Output relay 2 changeovers (TRIP, ALARM)
5 A (240 VAC)
Local signalling Green LED (power ON)
Red LED (TRIP)
Yellow LED (ALARM)
LED bar of insulation level
Mounting mode DIN rail 6 modules
Standards CEI-EN 61010-1
CEI-EN 61557-8
CEI-EN 61326-1
Weight 500g
Environment
IP degree of protection Front IP40 with cover
IP20 terminals
Relative humidity 5...90%
Operating temperature -10...+60 °C
Storage temperature -20...+70 °C