Since 30 years, our engineers and technicians design, manufacture and install radiation protection leaded and neutronic doors, wall shielding, partitions, cabinets and interlock transfer systems for Radiation Therapies and Nuclear Medicine installations worldwide. Whatever the size, the weight or the location DIB teams do their best to satisfy your requirements and to bring to you, your personnel and your customers a safe environment.
SAFETY – REABILITY – SPEED – SILENCE – EASY MAINTENANCE • Door and mechanism located outside bunker, access always possible, • Silent and Robust mechanism with high level torque, • Opening/Closing time starting at 10 s, • Electromagnetic clutch - adjustable torque due to a potentiometer, • Start and Stop go through a low speed, which enables a fl exible functioning and a precise stop, • Easy manual opening and closing with recessed handle.
RADIATION SAFETIES: 2 dry contact switches indicate that the door is closed and forbid accelerator running if door is not completely closed. Option: Sound bell when closing the door Last Man Out button
MECHANIC SAFETY In case of unusual opening or closing time, mechanism is declutch, door and motor stop after a time. DOOR CONTROL Opening, Half Opening on both sides of the door Closing, on outside of the door, 3 positions key button outside with automatic, manual mode and close position locked, Declutch manual mode/ automatic button inside for easy manual mode Option : Remote control button. OTHER (Contact us) Fixed frame or partition around passage door with lead/steel/paraffin or polyethylene instead of concrete.