Diagnostic test system for power apparatus condition assessment.
Applications
Loss angle (Power Factor/Tan δ), capacitance and inductance measurements on high voltage equipment
top↑
User Benefits
Easy, automated measurement
Accurate and powerful
Field-rugged and reliable
Immune to external interference due to line frequency modulation technique
top↑
Specifications
Voltage Range: 0 to12kV
Output Power: 3kVA
Output Current: 100mA continuous, 300mA >4 minutes, at 10kV
Output Frequency: 45 to 70 Hz
Current Measurement Range: 0 to 5A
Current Measurement Accuracy: ±1% of reading, ±1μA
Power Factor/Tan δ Range: 0 to 100% PF, 0 to 999.99% Tan δ
Power Factor/Tan δ Accuracy: ±0.04% PF/Tan δ of reading
Capacitance Range: 0 to 5μF
Capacitance Accuracy: ±0.5% of reading, ±1pF
Inductance Range: 10mH to 6H
Inductance Accuracy: ±0.5% of reading
Watts Range: 0 to 2kW
Watts Accuracy: ±2% of reading at 10kV, ±0.03% of VA, ±0.5mW
PC Communications: RS232 or USB
Operating Temperature: -20° to +50° C
Weight: 43kg