Item number: 9006301016
Application
The EE1800 with three-stage float control has been developed for wall-mounted and cassette units. With the exact same dimensions as the EE2000, the EE1800 offers significantly more pumping performance thanks to its performance-optimised drive. It is therefore suitable for air conditioning units up to 20 kW.
Description
The EE1800 comprises a pump and a float module. The three-stage float switch controls the pump. If the maximum permissible level of condensate is exceeded, the float triggers an alarm. The float module is connected directly to the outflow pipe of the condensate vessel or to the end of the outflow line. The supplied package includes the pump, the sensor, the vibration dampers and fastening materials.
Technical data
Drive - Swiss drive inside
For air conditioning units up to (kW) - 20
Pump module (L x W x H in mm) - 77 × 37,5 × 62
Electrical data - 230 V, 50/60 Hz, 8 W
Power consumption in Standby mode (W) - Operation 14, Standby 1
Float module (L x W x H in mm) - 82 × 39 × 39
Max. delivery volume (l/h) - 18
Max. head height (m) - 2,5
Alarm circuit - max. 230 V, 8 A (ohmic load) NO/NC normally open/normally closed
Special feature - Impervious to blockage or contamination due to unique valve design and large piston bore
Switching points (mm) - Alarm: max. 23 Start: 20 ±1 Stop: 15 ±1