Power supply 1~50/60 Hz 230V ±10%;
Auxiliary circuits in low voltage;
2 Normally close contacts for start pressure switches;
2 Contacts from external batteries for starting motor and auxiliary circuits power supply;
Contact for signal from priming tank;
Contact for signal from pressure switch of system in pressure/pump off;
Key-selector for AUT-EMERGENCY;
Push-buttons for manual Start/Stop of the pump;
Push-buttons for faults reset;
Push-button for manual start test (active in case of autostart failed);
Push-buttons for checking the control unit’s LED;
Push-button for manual emergency start protected by “Safe crash”;
LCD for monitoring: n.2 batteries volt and ampere, round counter, total and partial hour counter, fuel level indicator, water and oil temperature, oil pressure, start counter and events chronology;
LED for signals;
Operation mode according to UNI10779;
LCD in 5 languages: Italian, English, French, Spanish, German;
Specific alarms and delays settable on the electronic unit;
Alarm outputs for : auto mode excluded, failure on control panel, diesel pump running, start failed;
2 Battery chargers 12Vdc 3A (24Vdc 3A for 24V version);
Auxiliaries and motor protection fuses;
Main switch interlocking door;
Metallic box, IP55;
Ambient temperature: -5/+40 °C;
Relative humidity 50% at 40 °C (not condensed).