Multi genset load sharing (up to 32 gensets)
kW and kV Ar load sharing
Busbar voltages and frequency measurements
Dead bus sensing
Bus failure detection
Sequential set start
Equal aging of gensets
Logic Controller functionality for PLC
SNMP feature for ethernet communication
LCD Languages - English, Turkish
Inputs - 13x Configurable digital, 4x resistive configurable input, Magnetic Pickup,
Charge Alternator D+(WL) inputs
Outputs - Configurable 2x Relays, 7x Transistors, GBR outputs
Current Measurement - 3 phase generator
3-300 Vac Phase-Neutral, 5-99.9 Hz. Accuracy: scale %1 Resolution: 1V, Harmonic: up to 11 harmonics.
Voltage Measurement - 3 phase generator, 3 phase busbar
3-300 Vac Phase-Neutral, 5-99.9 Hz. Accuracy: scale %1 Resolution: 1V, Harmonic: up to 11 harmonics.
Case
Dimensions - 276 mm x 189 mm x 45 mm.
Protection Class - NEMA 4X IP65 at front side
Operating Range
DC Battery Supply range - 8 to 32Vdc, max.operating current is 360mA
Sender Measurement - 0 to 1300 ohm, accuracy: 1%FS, resolution: 1 ohm
Cabin.Temp.Measuremet - -50 to +100 ºC, accuracy: 1 % FS, resolution: 1 ºC.
Operating / Storage Temp. - -20°C with +70°C / -40°C with +80°C
Expansions
Internal - USB programming and communication port, CanBus communication with 1939 ECU, CanOpen, Ethernet, RS485
GPRS - Optional
Embedded WEB server - Optional
Serial ModBus -
Approvals - CE, GOST-R