OPERATION
2/2-ways. Servo-assisted. Normally closed.
When the coil is energized the plunger opens
a pilot drilling where the media, which is on
top of the diaphragm and keeps it closed, is
released. The input pressure lift the diaphragm
and opens the valve.
When the coil is de-energized the plunger
closes the pilot drilling,that pressure is restored
on top of the diaphragm, causing the valve to
shut.
The minimum pressure (0,5 bar) is absolutely
necessary as pressure difference between
input and output of the valve.
CONNECTION
B.S.P. threaded connection GVa - G1
(DIN ISO 228 T1)
welded connection acc. to DIN 3239
welded connection acc. to DIN 11850-2
welded connection acc. to ISO 4200
Flanged connection PN16
CABLE CONNECTION
AC or DC with connection socket according
to DIN 43650
VOLTAGES
12, 24, 110, 196 V (DC)
24, 42, 110, 230V50HZ (AC)
POWER CONSUMPTION
11 watts, 24/15 VA
MATERIAL
Body:
Internal parts
Sealing:
Stainless Steel 1.4408
Stainless steel
NBR(FKM, EPDM)