The system is consisted by below units
-Variable Frequency Power supply
-Exciting Transformer
-HV Reactor
-Capacitive Divider
-Accessories Carrycase (connection wires)
Application and requirement
1. The 35kV/300mm2 cable is 800m, the capacitance is ≤0.15μF, the test frequency is 30-300Hz, and the test voltage is 52kV.
2. 10kV/300mm2 cable 2000m, electric capacity ≤0.74μF, test frequency 30-300Hz, test voltage 22kV.
3. 35kV switchgear, circuit breaker, insulator and busbar AC withstand voltage test, the test frequency is 30-300Hz, and the test voltage does not exceed 100kV.
4. 10kV motor AC withstand voltage test, the test frequency is 45-65Hz, and the test voltage does not exceed 15kV.
5. AC withstand voltage test for transformers with 35kV less than 50000KVA, capacitance ≤0.02μF, test frequency 30-300Hz, and test voltage 85kV.