Safety switch CET-AS – with AS-i connection, closed-circuit current principle, with wire front release (bowden) 4 m
• Safety switch with guard locking and integrated evaluation electronics
• Locking force up to 6,500 N
• Category 4 / PL e according to EN ISO 13849-1
• Unicode
• Wire front release (bowden), automatic return, rope length 4 m
• Approach direction A (delivery state)
Guard locking type
CET3
Closed-circuit current principle, guard locking by spring force. Release by control of AS-i output 0.
Control of the guard locking solenoid
The guard locking solenoid is controlled by the control system via ASInterface bus bit D0.
AS-Interface inputs
D0, D1
Door monitoring
D2, D3
Guard lock monitoring
Evaluation is performed via a safety monitor.
AS-Interface outputs
D0
Guard locking
D1
LED red
D2
LED green
LED function display
The ASI LED indicates the operating voltage on the bus.
The State LED indicates if a fault has been detected on the AS-Interface bus.
The green and the red LEDs can be controlled as required by the control system via the bus using bits D1 and D2.