Housing
Frame made of painted galvanised steel heavy profiles to ensure
total mechanical and corrosion resistance.
Compressor
Reciprocating SEMIHERMETIC type, fixed on vibration isolation
mountings; complete with oil pump, crankcase electrical heater,
electronic protection, intercepting valves on suction and discharge
(mod. 015-20 HP); flexible joints on suction and discharge.
Water heat exchanger
Shell and tube type, thermally insulated by vapour-proof closed cell.
Electrical board
Switchboard to standards IEC 204-1/EN60204-1, complete with contactor
and protection for compressor. Main isolator and door interlock
safety device.
Control
The microprocessor controls the unit capacity by timing the compressors
and checks the operating alarms with the possibility to
connect to BMS.
Refrigerant circuit
Filter dryer, moisture-liquid sight glass, solenoid valve, intercepting
valve on the liquid line, HP and LP pressure switches, cycle reversing
valve, gas separator and liquid receiver thermostatic expansion
valve.
Refrigerant charge
The condenserless units are shipped with a maintenance charge
of nitrogen.