The expansion I/O modules include basic DI/O, AI/O and other communication modules, also include thumbwheel switch input module, 16/7 segment LED display module, 8 types (J, K, R, S, E, T, B, N) thermocouple, Pt100, Pt1000 RTD temperature measurement modules. There is also a new additions to the range including load cell module used in weighting, potential meter module used in measuring position, and a user-friendly voice module.
Number of channel 4 channels
Resolution 14 or 12 bits
Occupied I/O points 4 IR (input registers) and
1 unused OR (output register)
Conversion time Conversion once for each scan
Accuracy ±1%
Potential meter
impedance 1K~10KΩ
Voltage Input Range 0~10V
Potential meter voltage 10V
Filters Moving averages
Isolation method Transformer and optical isolation,
500VAC, 1 minute
Power consumption 24VDC, -15%/+20%, 2W
Wiring mechanism 7.62 mm fixed terminal block