The expansion I/O modules include basic DI/O, AI/O and other communication modules, also include thumbwheel switch input module, 16/7 segment LED display module, 8 types (J, K, R, S, E, T, B, N) thermocouple, Pt100, Pt1000 RTD temperature measurement modules. There is also a new additions to the range including load cell module used in weighting, potential meter module used in measuring position, and a user-friendly voice module.
6 channels, 14-bit analog input module
Input/Output value -8192~8191 or 0~16383 (14-bit)
Input/output
Signal range
Bipolar Voltage: -10~10V or -5~5V Current: -20~20mA or -10~10mA
Unipolar Voltage: 0~10V or 0~5V Current: 0~20mA or 0~10mA
Maximum resolution Voltage: 0.3mV (5V/16384) Current: 0.61μA (10mA/16384)
Accuracy ± 1%
Conversion time Conversion once for each scan
Maximum input signal Input voltage: ±15V Input current: ±30mA —
Allowable load range — Output voltage: 500Ω~1MΩ Output current: 0~500Ω
Input impedance Input voltage: 63.2KΩ Input current: 250Ω —
Isolation method Transformer(power) and optical(signal) isolation, 500VAC, 1 minute, no isolation between each channel
Power consumption 24VDC -15%/+20%, 3.2W max.
Wiring mechanism 7.62 mm fixed terminal block