Fire Resistance Water Spray Tester, CFW-820, BS 6387
FESTEC’s BS 6387 Tester, BS 6386 standard is belong to British, is a testing device that checks for the standard level of current in the cable, and also checks the cable’s resistance for heat and water of the cable.
• BS 6387 - Performance requirements for cables required to maintain circuit integrity under fire conditions – Annex D.3 Resistance to fire with water
• Test Chamber Assembly
- Dimension : 1,220(W) x 940(D) x 900(H) mm
- Material : Stainless Steel 304
• Water Tank
- Dimension 1,180(W) x 1,250(D) x 350(H) mm
- Material : Stainless Steel 304
- Water Capacity : 230±30 L
• Pump Assembly
- Dimension : 460(W) x 285(D) x 405(H) mm
- Rpm : 750 ~ 1,200 Rpm
- Pressure : 12 ~ 40 Kg/Cm
• Calibration container
• Heat Source
- Ribbon type Propane Gas Burner
- Material : Stainless Steel
- Dimension of Burner Face : (L) 400 x (W) 10 mm
- Space of Hole : 3.2mm from one another
- Mixing System : Venturi Type Mixer
• Mass Flow Controller(MFC)
- Gas : Propane(C3H8)
- Flow Rate : 15 SLPM
• Mass Flow Controller(MFC)
- Gas : Air
- Flow Rate : 180 SLPM
• Pressure Gauge
• solenoid Valve
• Flashback Arrestor
• Electric Control
- Transformer & Slidac(Slide-AC) : 3 phase 3wire, 100 ~ 1,000V
- Indicator : AC 220V, M80 AC 1,000V