Input: Resistive sensors, TC, resistance, voltage
Galvanic isolation: 1500V AC
Accuracy: <0.1% F.S. or <0.5°C
Models: Standard and ATEX
Configuration With PC (Microsoft Windows only) and with HART protocol
EC Type examination certificate number:
INERIS 13ATEX0015X (Ex ia)
INERIS 13ATEX3006X (Ex nA)
IECEx conformity certificate:
INE13.0022X (Ex ia)
INE13.0023X (Ex nA)
ATEX/IECEx classification
II 1 G Ex ia IIC T4 Ga
II 3 G Ex nA IIC T4 Gc
II 1 D Ex ia IIIC T135°C Da
Function
Tia3 temperature converters are aimed at converting signals coming from large panel of input signals:• Coversion of temperature measurement with RTD100, RTD1000, Ni100, Ni1000 or thermocouple.• Conversion of linear resistance variation (from level sensors or valves).• Voltage (mV) and ohmic measurement.DIN rail mountingCertified to be installed in explosive atmosphere (see codification).
Electrical data
Input Programmable (refer to backside)
Power supply
Standard model 10V ... 30 Vdc
ATEX version 10V ... 28 Vdc
Galvanic isolation 1500V CA
Accuracy≤ 0.1% F.S. or ≤ basis accuracy (refer to backside) according to the most important valueLoad resistance(Vsupply-10) / 0.0215 Ω
Shorted or broken line detection:
Configurable 3.5 mA to 21.5 mA (NAMUR NE43)
Warm-up time5 minutes
Response time < 2 s
Voltage supply ≤ 0.01% of the current in the loop for a variation of 0.1% of Vsupply
Temperature ≤ 10% of accuracy / degree
Error due to CJC1.5x basis accuracy for a cold junction at 0°C to be added
Line resistance effect
RTD100 2wires* / 3wires** 2.5°C/ Ω
RTD1000 2wires* / 3wires** 0.25°C/ Ω
Ni100 2 wires* / 3 wires** 2°C/ Ω
Ni1000 2 wires* / 3 wires** 0.2°C/ Ω