Version: With capillary
Case: Composite material
Sensing element: Copper bulb and capillary
Switch: 1 switch
Options:
» SIL capability
» APSAD
Function
Instruments from this series are fitted with a flexible arm mechanism 1 which allows the device to withstand impacts or vibrations without set point drifting
As load created by the sensing element 2 is directly opposed to the load from the spring 3, this arm undergoes no force which allows a linearity of measurement and dead band (Patent n° 86.08.498).Set point is selected through external screw 4 while dead band 5 is adjusted from inside.
Housing Fiber glass and polyarylamid Cover in
polycarbonate
Protection IP65
Sensing element
Pressure switch NBR diaphragm, flange in brass
Connection 1/2 BSP male according to EN837-1
Options FKM diaphragm for oxygen cleaning
EPDM diaphragm
Other connections on request
Temperature switch 2 meters capillary
Bulb Ø9x120mm in copper
Accessories Bulb mechanical protection in brass or st.st.
Capillary compression gland
Screws Galvanized steel
Electrical connexion Cable gland ISO M20
3 wires internal terminal (2.5 mm² )
Working T° -20 to 60°C
Process T° -20 to 100°C (pressure)
Weight 450 gr
Current rating mentioned here above allow following cycles :
Code 06 : 300.000 to 500.000 cycles