Input: RTD100 2 or 3 wires
Output: 4-20mA
Accuracy: <0.1% F.S. or <0.5°C
Models: Standard and ATEX
Configuration With PC (Microsoft Windows only)
EC Type examination certificate number:
INERIS 08ATEX0004X & 08ATEX3004X
NAMUR NE43 Upscale 21.5 mA
ATEX classification
Ex ia IIC T6/T5/T4
Ex iaD 20 T85/T100/T135 °C
II 3 G Ex ic IIC T6/T5/T4
Function
TiXo1 temperature converters aimed at converting signals from RTD100 sensor to a standard 4 to 20mA current signal.Head mounting product.It is certified to be located in hazardous area (See codification).
Electrical data
Input RTD100 2 or 3-wires according to EN60751
Max measuring range -220 to 850°C
Minimum span 10°C
Output4/20 mA
Power supply
Standard model 8V ... 30 Vdc
ATEX version 8V ... 28 Vdc
Accuracy≤ 0.1% F.S. or ≤ 0.5°C
according to the maximal value
Load resistance(Vsupply-8) / 0.0215 Ω
Shorted or broken line detection
Configurable 3.5 mA to 21.5 mA
NAMUR NE43 Downscale 3.5 mA
Drift
Voltage supply: ≤ 0.01% of the current in the loop for a variation of 0.1% of Vsupply
Temperature:≤ 10% of accuracy / degree
Line resistance effect
2-wires RTD 2.5 °C / Ω, compensation is configurable
3-wires RTD 2.5° C / Ω between wires
EMC Immunity< 0.1% F.S
Housing Plastic (PBT)
Ø = 44 mm H = 21.6 mm
Protection IP 00 on terminals
Weight approx. 40 g
Working T°-40°C to 85°C (non ATEX version)
Storage T°-40°C to 85°C
Relative humidity5%-95% without condensing
Connection Screw terminals – capture screws
Max. wire size1x 1.5 mm²