Relative pressure transmitter FKG series
membrane4-20 mAHART

Relative pressure transmitter - FKG series - GEORGIN S.A. - membrane / 4-20 mA / HART
Relative pressure transmitter - FKG series - GEORGIN S.A. - membrane / 4-20 mA / HART
Relative pressure transmitter - FKG series - GEORGIN S.A. - membrane / 4-20 mA / HART - image - 2
Relative pressure transmitter - FKG series - GEORGIN S.A. - membrane / 4-20 mA / HART - image - 3
Relative pressure transmitter - FKG series - GEORGIN S.A. - membrane / 4-20 mA / HART - image - 4
Add to favorites
Compare this product
 

Characteristics

Pressure type
relative
Technology
membrane
Output
4-20 mA, HART, Modbus, Profibus
Supply voltage
DC
Mounting
flange
Process connection
NPT 1/4
Material
stainless steel
Protection level
intrinsically safe, explosion-proof
Applications
process
Other characteristics
smart
Pressure range

Min.: -1 bar
(-14.5 psi)

Max.: 500 bar
(7,251.89 psi)

Precision

0.07 %

Long-term stability

0.1 %

Process temperature

Min.: -40 °C
(-40 °F)

Max.: 100 °C
(212 °F)

Description

SMART Transmitter, 4-20mA + HART protocol Rangeability : 100:1 Power supply : 10.5 to 45VDC Process wetted parts material : Inox 316L, Hastelloy, Monel, Tantalum, … Process connection : ¼”-18NPT (oval flanges on request) Burnout according NAMUR NE43 recommandations Options: » Local analog or digital Indicator » Intrinsically safe version » Explosion proof version » FM, CSA and IECEX certification » Stainless Steel electronic housing The ProcessX pressure transmitter accurately measures gauge pressure and transmits a proportional 4 to 20 mA signal.The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor technol-ogy to provide exceptional performance and functionality FEATURES 1. Hig Haccuracy up to ±0.04% 0.065% accuracy as standard. Georgin’s micro-capaci-tance silicon sensor assures this accuracy for all elevat-ed or suppressed calibration ranges without additional adjustment. 0.04% accuracy as option. 2. MiniMuM inventory and design Electronics unit, local indicators and electronics hous-ing are interchageable among all ProcessX transmit-ters. 3. MiniMuM environMental inFluence The “Advance Floating Cell” design which protects the pressure sensor against changes in temperature, and overpressure substantially reduces total measure-ment error in actual field applications.

Other GEORGIN S.A. products

Measurement