The 24/220Vdc/Vac Transistor-Out Detector D5093 module is a unit suitable for applications requiring SIL 3 level in safety related systems for high risk industries. Each channel is able to reflect the presence of a 24 to 220 Vac/Vdc input signal to the output by closing an optically coupled NO open-drain transistor (solid-state relay, MOSFET output). The presence of the 24 to 220 Vac/Vdc input signal is also indicated by a yellow LED on the front panel. The input switching voltage levels are selected, according to the applied input signal, by means of an internal dip-switch (overload protected).
FEATURES
SIL 3 / SC 3
Installation in Zone 2/Div. 2
2 fully independent channels
Two port isolation, Input/Output
High Density, two channels per unit