The METRAclip 87 clamp multimeter is suitable for the measurement of medium power values in the low-voltage range, and thus offers optimized safety for all types of systems and under any measuring conditions. In addition to applications in the areas of maintenance, troubleshooting and repair, the METRACLIP is also used for measurements in railway systems and low-voltage distribution networks.
Clamp opening: 48 mm
Current: AC 99,99 / 999,9 A rms bei 10 Hz - 2 kHz
DC ±99,99 / ±999,9 / ±1500 A dc
AC+DC 99,99 / 999,9 A rms
99,99 / 999,9 / 1500 A peak
Inrush current: 10 ..1000 A rms / 1500 A peak
Voltage: AC 99,99 / 999,9 V rms bei 10 Hz - 3 kHz
DC ±99,99 / ±999,9 V dc
AC+DC 99,99 / 999,9 V rms
99,99 / 999,9 / 1500 V peak
Frequency: f (Uac) 5,0 Hz ..19,99 kHz
f (Iac) 5,0 Hz ..1999 Hz
Power: Active power: 9999 W / 99,99 / 999,9 / 1500 kW
Apparent power: 9999 VA / 99,99 / 999,9 / 1500 kVA
Reactive power: 9999 var / 99,99 / 999,9 / 1500 kvar
PF -1,00 ..+1,00
DPF 0,00 ..1,00
Distortion: Ripple 0,1 ..1000 %
CF 1,00 ..10,00
THDr / THDf 0,0 ..100 % / 0,0 ..1000 %
Harmonicals H01 ..H25