Transformer containment bund BDRG-2
siliconegalvanised steelsheet steel

Transformer containment bund - BDRG-2 - Groupe SANERGRID - silicone / galvanised steel / sheet steel
Transformer containment bund - BDRG-2 - Groupe SANERGRID - silicone / galvanised steel / sheet steel
Transformer containment bund - BDRG-2 - Groupe SANERGRID - silicone / galvanised steel / sheet steel - image - 2
Transformer containment bund - BDRG-2 - Groupe SANERGRID - silicone / galvanised steel / sheet steel - image - 3
Transformer containment bund - BDRG-2 - Groupe SANERGRID - silicone / galvanised steel / sheet steel - image - 4
Transformer containment bund - BDRG-2 - Groupe SANERGRID - silicone / galvanised steel / sheet steel - image - 5
Transformer containment bund - BDRG-2 - Groupe SANERGRID - silicone / galvanised steel / sheet steel - image - 6
Transformer containment bund - BDRG-2 - Groupe SANERGRID - silicone / galvanised steel / sheet steel - image - 7
Transformer containment bund - BDRG-2 - Groupe SANERGRID - silicone / galvanised steel / sheet steel - image - 8
Transformer containment bund - BDRG-2 - Groupe SANERGRID - silicone / galvanised steel / sheet steel - image - 9
Transformer containment bund - BDRG-2 - Groupe SANERGRID - silicone / galvanised steel / sheet steel - image - 10
Transformer containment bund - BDRG-2 - Groupe SANERGRID - silicone / galvanised steel / sheet steel - image - 11
Transformer containment bund - BDRG-2 - Groupe SANERGRID - silicone / galvanised steel / sheet steel - image - 12
Transformer containment bund - BDRG-2 - Groupe SANERGRID - silicone / galvanised steel / sheet steel - image - 13
Add to favorites
Compare this product
 

Characteristics

Applications
for transformers
Material
silicone, sheet steel, galvanised steel
Other characteristics
rigid, for indoor use
Capacity

Min.: 150 l
(39.6 gal)

Max.: 5,000 l
(1,320.9 gal)

Description

S235 steel tank, sheet thickness from 20 to 30/10 2 removable walls: 1 long and 1 wide to be bolted on with pan bolts on lock nuts (supplied) Technical seal in special SILGRID™ silicone with high temperature resistance and hot dielectric oil on all removable parts of the tank, to be applied after installation of the transformer in the tank and closure of the fronts in order to guarantee complete sealing of the tank Unit quality inspection before leaving the factory, with the bins arriving pre-assembled with their bolts and nuts pre-installed. Earthing output available at 2 opposite points (terminal not supplied) Double-sided watertight welding, welding process regularly tested by third-party inspection bodies using the ARDROX 996 P2 dye penetrant method or equivalent. By default, our BDRG-2 containers are hot-dip galvanised to guarantee superior internal and external performance compared with C3 paint. They are certified hot-dip galvanised in accordance with ISO EN1461-2022. The BDRG-2 range comprises 14 standardised drip trays for ECODESIGN Tier 2 distribution transformers. This means that the required retention volume can be met, as well as the length and width of your transformers. Please note that since the AFNOR update in 2021 on the NFC13200, simple retention tanks not equipped with fire-stop shutters on the inside and whatever the power, are no longer authorised. We recommend that you consult us if you have any problems with heightening or dimensions, and that you contact our inspection body, such as APAVE, SOCOTEC or Bureau Veritas (or other), to obtain the necessary exemptions from your insurance organisations. Depending on the configuration of your project,

Catalogs

No catalogs are available for this product.

See all of Groupe SANERGRID‘s catalogs
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.