The Euro system separator GENO®-G5 protects the drinking water network against liquids up to and including liquid category 5 (in accordance with DIN EN 1717). It prevents the backflow, back pressure and return suction of modified drinking water into the drinking water network. GENO®-G5 is particularly suited to the dental field for supplying dental treatment units. We recommend the installation of the optional rinse unit here. For automatic disinfection, we suggest installing dosing system GENODOS® DM-B downstream. The system separator is designed as a ready-to-connect compact device with an aluminium profile frame with adjustable feet, with full piping and wired ready for connection.
Nominal connection diameter: 3/4"
Nominal flow: 2 m³/h
Nominal pressure: PN 10 bar
Pressure boosting device
DVGW-certified
Installation requirements
Observe local installation directives, general guidelines (e.g. WVU, EVU, VDE, DIN, DVGW, and/or ÖVGW or SVGW) and the system's technical specifications. The installation site must be accessible for maintenance work, flood and frost-proof and ensure that the system is protected from chemicals, dyes, solvents and vapours. The system must not be operated in a dusty environment or if acids and corrosive or potentially explosive gases are present. A fine filter must be installed directly upstream of the system and shut-off devices must be provided in the on-site installation on the system's inlet and outlet.