Using the H-armature principle the polarised latching relays are noted for their high resistance to shocks and vibrations. They are always in a defined switching position and therefore there is no loss of information in case of power failure. The advantage of polarised latching relays is the pulse driven operation of some milliseconds, coil heating can be neglected.
The relays are designed and manufactured in accordance to international standards of IEC 61810 part 1 as well as they meet the UC3 requirements for Supply Control Switches as of IEC 62052 part 31.
Technical data
Coil data
Rated power 8 W
Operating power to set 6 W
Pulse to set 30 ms
Action time < 15 ms
Contact data
Max. contact arrangement 2 a
Contact material AgSnO2
Max. switching power 25,000 VA
Mechanical life 106
Insulation
Creepage and clearance distance coil – contact 8 mm
Test voltage coil – contact 4,000 V eff.
Test voltage contact – contact 4,000 V eff
Test voltage open contact 1,000 V eff.
Dielectric strength coil – contact 12 kV / 1.2 / 50 μs
General data
Ambient temperature -40 ... +85 °C
Weight 150 g
Conform to VDE, UL, CSA, SEV, SEMKO