Rotary actuator for adjusting dampers in HVAC installations
•Control2-/3-point
•Feedback
potentiometerP5 = 5 kΩ
•Damper sizeup to approx. 2 m²
•Shaft couplingclamp
◊ 8-15 mm / Ø 8-20 mm
Electrical data
Nominal voltage range : 19...29 VAC/DC
Power consumption motor (motion) : 2,0 W
Power consumption standby (end position) : 1,0 W
Wire sizing : 3,5 VA
Control : 2-/3-point
Feedback signal : potentiometer P5 = 5 kΩ
Auxiliary switch : -
Contact load : -
Switching point : -
Connection motor : cable 1000 mm,
3 x 0,75 mm² (halogen free)
Connection feedback potentiometer : cable 1000 mm,
3 x 0,75 mm² (halogen free)
Connection auxiliary switch : -
Connection GUAC : -
Functional data
Damper size : up to approx. 2 m²
Synchronised speed : ±5%
Direction of rotation selected by switch
Manual override : gearing latch disengaged with
pushbutton, self-resetting
can be limited with adjustable
mechanical end stops