Rotary actuator for adjusting air dampers for pressure control in HVAC installations
•Control(0)2...10 VDC
•Sensor300 Pa (dynamic)
•Damper sizeup to approx. 2 m²
•CommunicationPP-Bus
•Shaft couplingclamp
◊ 8-15 mm / Ø 8-20 mm
Technical data
Electrical data
Nominal voltage range : 19...29 VAC/DC
Power consumption motor (motion) : 2,5 W
Power consumption standby (end position) : 1,5 W
Wire sizing : 5,0 VA
Control : (0)2...10 VDC / Ri > (100 kΩ) 50 kΩ
(0)4...20 mA / Rext. = 500 Ω
Feedback signal : (0)2...10 VDC, max. 0,5 mA
Priority control : closed / Pmin / Pmax / open
Connection motor : cable 1000 mm,
4 x 0,75 mm² (halogen free)
Connection GUAC : -
Connection GUIV : via diagnostic connector and
feedback signal U
Communication : PP-Bus (1200 Bd, max. 15 VDC)
Sensor
Calibration : 300 Pa, height adjustment necessary
(300 Pa = 1,2 in H2O), dynamic measurement principle
Measuring range : 0...300 Pa
Burst pressure : 1 bar
Nominal value : Pmin / Pmax / Pconst based on Pnom
Media : air
0...70°C / 5...95% r.H.,
non condensing
Mounting position : independent of position
Connection : Ultem 2200 / tube clip Ø 4-6 mm