Universal-Controller for two motorized fire protection dampers for bus (Modbus oder BACnet) or analog integration into a superior system
Technical data
Electrical data
Nominal voltage : 230 VAC, 50/50 Hz
Nominal voltage range : 185…280 VAC
Power consumption : 2 W
Wire sizing : 2 VA + actuators (max. 24 VA)
Connection : AMP plug-in connections and screw terminals
Modbus
Protocol : Modbus RTU
Medium : RS-485, not electrically isolated
Number of nodes : 100
Baud rates : 9600 / 19200 / 38400 / 76800 Bd
Adress : 1…127
(1-10 reserved for M200 / 0 reserved for broadcast)
Termination : 120 Ω line termination in the device on extra pin
(if last device in the line)
Response time : < 200 ms
BACnet
Protocol : BACnet MS/TP
Medium : RS-485, not electrically isolated
Number of nodes : 65
Baud rates : 9600 / 19200 / 38400 / 76800 Bd
(auto detect)
BACnet instance number : automatically assigned by
physical address, writable
Termination : 120 Ω line termination in the device on extra pin
(if last device in the line)
Response time : < 100 ms
Safety
Protection class : II (double insulation)
Degree of protection : IP 42